English中文
On the standard of air supply speed in various occasions
1、 Recommended flow rate for louvers
position Fresh air Return air Front of dehumidifier Desuperheater bypass Heater bypass
Current Speed m/s 2.5~4 6~6 2~4 7.5~12 5~7.5

2、 Air volume index and indoor average flow of different air supply modes
Air supply mode Of unit floor area
Air supply volume l/s m
Workspace Average
Velocity m/s
Ventilation rate 1/h
Side air supply shutter
Strip vent
Local orifice plate air supply
Ceiling diffuser
Ceiling orifice plate air supply
3~6
4~10
5~15
5~25
5~50
0.13~0.18
0.10~0.18
0.10~0.18
0.10~0.25
0.05~0.15
7
12
18
30
60

3、 RECOMMENDATIONS AND MAXIMUM VELOCITIES FOR LOW SPEED DUCT SYSTEMS
Application site residence Public buildings factory
recommend maximum recommend maximum recommend maximum
Outdoor air inlet
Air filter
Heating manifold
Cooling stack
Drenching room
Fan outlet
Main air duct
Branch air duct (horizontal)
Branch air duct (vertical)
2.5
1.3
2.3
2.3
2.5
6.0
4.0
3.0
2.5
4.0
1.5
2.5
2.3
2.5
8.5
6.0
5.0
4.0
2.5
1.5
2.5
2.5
2.5
9.0
6.0
4.0
3.5
4.5
1.8
3.0
2.5
2.5
11.0
8.0
6.5
6.0
2.5
1.8
3.0
3.0
2.5
10.0
9.0
5.0
4.0
8.0
1.8
3.5
3.0
2.5
14.0
11.0
9.0
8.0

4、 Maximum allowable velocity of air supply area of low-speed air duct system
Application site Noise control of main air duct Conduct is controlled by friction resistance
Air supply main pipe Return air main pipe Air supply main pipe Return air main pipe
residence
Apartment and hotel rooms
Office and library
Auditorium and theater
Banks and high-end restaurants
Department stores and cafeterias
factory
3.0
5.0
6.0
4.0
7.5
9.0
12.5
5.0
7.5
10.0
6.5
10.0
10.0
15.0
4.0
6.5
7.5
5.5
7.5
7.5
9.0
3.0
6.0
8.0
5.0
8.0
8.0
11.0
3.0
5.0
6.1
4.0
6.0
6.0
7.5

5、 Relationship between flow velocity in stay area and human sensation
Velocity m/s Human sensation
0~0.08
0.127
0.127~0.25
0.33
0.38
0.38~1.52
Uncomfortable, feeling of stagnant air
Ideal and comfortable
Basic comfort
Uncomfortable, can blow tissue
Upper limit of comfort for standing people
For plant and local air conditioning

6、 Maximum allowable flow velocity in the stay area
Human condition Sitting for a long time Sit for a short time Light work Rework
application office restaurant Store light industry Factory and dance hall
冷却 m/s
加热 m/s
0.10
0.20
0.15
0.30
0.20
0.35
0.30
0.45

7、 Recommended flow rate of return air grille
position Near seat Above the stay area Lower part of door Upper part of door Industrial
Velocity m/s 2~3 3~4 4 3 >=4

8、 Maximum allowable air supply temperature difference in air-conditioned rooms
Air supply mode Height of the following rooms m
2 3 4 5 6
Side air supply, large air volume
Side air supply, small air volume
Ceiling diffuser
6.5
9.0
9.5
8.3
11
16
10
13
17
12
15
18
14
17
18

9、 Flow rate of ventilation system
system businessIndustry
low speed Air supply, maximum flow rate
Air supply, general flow rate
Return air, maximum velocity
Return air, general velocity
13
6~11
10
7.5~9
13
11~13
13
9~13
High speed, general 13 13~25

10、 Recommended air supply outlet flow rate
Application site Velocity m/s
Broadcasting Room
theater
Residence, apartment, hotel room, classroom
Private office
General office
cinema
Department store, upper floor
Department store, underground
1.5~2.5
2.5~3.5
2.5~3.8
2.5~4.0
5.0~6.0
5.0
7.5
10.0

11、 Allowable supply air flow rate controlled by noise standard
Application site
Velocity m/s
Library, broadcasting room
Residence, apartment, private office, hospital room
Banks, theaters, classrooms, general offices, shops, restaurants
Factory, department store, kitchen
1.75~2.5
2.5~4.0
4.0~5.0
5.0~7.5
Chapter II Quick Reference Table of Air Volume at Air Supply Outlet
1、 Air supply volume of side air supply outlet

Size of air supply outlet mm Velocity of air supply outlet m/s
1.5 2.0 2.5 3.75 5.0
250*100 30 40 50 70 95
300*100 35 45 55 85 115
400*100 45 60 75 115 150
500*100 55 75 95 145 190
600*100 70 90 115 170 230
750*100 85 115 145 215 285
900*100 100 135 170 255 340
250*150 45 55 70 105 145
300*150 50 70 85 130 170
400*150 70 90 115 170 230
500*150 85 115 145 215 285
600*150 100 135 170 255 340
750*150 130 170 215 320 430
900*150 155 205 255 385 515
400*200 90 120 150 230 305
500*200 115 150 190 285 380
600*200 135 180 230 340 455
750*200 170 230 285 430 570
900*200 205 275 340 415 685
400*250 115 150 190 285 380
500*250 145 190 240 355 475
600*250 170 230 285 430 570
750*250 215 285 355 535 715
900*250 255 340 430 640 855
530*300 170 230 285 430 570
600*300 205 275 640 575 685
750*300 255 340 430 640 855
900*300 310 410 515 770 1030
1000*50 55 75 95 145 190
1000*75 85 115 145 215 285
1000*100 115 150 190 285 380
1000*125 145 190 240 355 475
1000*150 170 230 285 430 570
1000*175 200 265 330 500 665
1000*200 230 305 380 570 760
1、 Air supply volume of ceiling diffuser
Dimension mm Air supply flow m/s
1.0 1.5 2.0 2.5 3.75 5.0
250*250 50 70 95 120 175 235
300*300 70 100 135 170 255 340
350*350 90 140 185 230 350 465
400*400 120 180 240 295 440 590
500*500 190 280 380 470 710 945
600*600 270 410 545 680 1020 1360
2、 Fan matching air duct size
model 003#(50W) 004#(72W) 006#(115W) 008#(140W) 010#
(190W)
012#
(225W)
014#
(290W)
Dimension mm 600*200 750*200 830*200 950*200 1200*200 1300*200 1800*200