Product Overview
IN94 series temperature and humidity transmitter is used in standard HVAC environment, with anti condensation and extremely high protection performance. In the long-term use process, it can effectively avoid risks such as drift, corrosion and interference.
Main technical indicators
Measuring range: temperature: - 40 ℃~+125 ℃, humidity: 0 ~ 100% RH
Measurement accuracy: temperature: ± 0.3 ℃ (at 20 ℃); Relative humidity: ± 3% RH (20 ℃, 10-90% RH, standard atmospheric pressure)
Signal output: current output type: 4 ~ 20mA (two-wire system or three wire system), electrical load < 500 Ω
Voltage output type: 0 ~ 10V, electrical load>10K Ω
RS485 output type: standard ModBus RTU protocol
Power supply: 20~28VDC
Cable head: PG9, cable diameter: 4-8mm
Enclosure protection grade: IP65
Operating temperature: transmitter: - 40~+60 ℃ (without display), - 20~+60 ℃ (with display); Probe: - 40 ℃~+125 ℃
Storage environment: - 20 ℃~+60 ℃, 10%~85% RH
Circuit connection
Installation dimension drawing
Model Selection Table