application
Monitoring the pressure and differential pressure of air and non corrosive gas media can be applied in the following fields:
• Clean air conditioning and cleanrooms
• Intelligent building fan air conditioning filter screen
• Environmental protection
• Fan and blow control
• Filter and blow control
• Fluid and level control
• Gas flow control
model
Use a knob with measuring scale to adjust the differential pressure setting value of the differential pressure sensor:
model | Pressure adjustable upper limit from to |
930.80 | 20 - 300Pa |
930.81 | 40 - 100Pa |
930.82 | 40 - 200Pa |
930.83 | 50 - 500Pa |
930.85 | 200 - 1000Pa |
930.86 | 0.5K -2.5KPa |
930.87 |
1K - 4KPa |
The differential pressure switch shall be used for vertical installation. We recommend the pipe connection with the interface facing down. If the switch is installed horizontally with AMP connector, the differential pressure may be 20 Pa higher than the actual value.
The maximum working pressure is 10K Pa in all ranges
Medium air, non combustible and non corrosive gas
temperature range
Medium and ambient temperature from - 20~85 ℃
Storage temperature - 40~85 ℃
Diaphragm Material
Silicone at 200 ℃
Pressure connection
Two plastic pipe connecting pieces P1 and P2, with an outer diameter of 6mm,
P1 is connected to high voltage, marked with+
P2 is connected to low voltage, marked with -
Housing material
The body is PA6.6
Enclosure is PS
weight
With shell: 150g
Without shell: 110g
Mechanical working life
More than 1 million switches
Electrical rated parameters
Standard model: max.1.0A (0.4A)/250VAC
Low voltage model: max.1.0A/24VDC
Electrical connection
AMP float inserted 6.3mm × 0.8mm, DIN standard: 46244, or button type threaded terminal.
Cable PG-11 or M20 × one point five
Degree of protection
IP54 with housing
authentication
73/23/EEC for CE certified low-voltage electrical equipment