YGM105Differential sensor
Product Overview
YGM105The water pipe temperature transmitter adopts the structure of sensing and transmitting integration. The temperature sensing element is a high-precision platinum resistance, which has the characteristics of wide measurement range, fast response, good interchangeability, stable performance, etc. Two point calibration can be realized by using the potentiometer on the circuit board.
Technical indicators
Measuring range: 0~100 ℃
Accuracy: ± 0.3 ℃ (25 ℃, standard atmospheric pressure)
Response time: T90 with bushing ≤ 18s; Without bushing T90 ≤ 10 seconds
Output signal: current output type: 4 ~ 20mA (two-wire system) electrical load<400 Ω
Voltage output type: 0 ~ 10V (three wire system) electrical load>10K Ω
Resistance output type: PT100/PT1000 optional
Power supply: 24VDC ± 10%
Cable lock: M16 × 1.5, cable diameter: 4-8mm
Enclosure protection grade: IP54
Temperature sensor probe protection: stainless steel pipe
Working temperature of probe: 0~100 ℃
Working temperature of transmitter: - 20~50 ℃
Storage environment: - 10~+60 ℃, 0~90% RH, no condensation
Applicable medium: water or non corrosive liquid
characteristicAccuracy: ± 0.3 ℃ (25 ℃, standard atmospheric pressure)
Response time: T90 with bushing ≤ 18s; Without bushing T90 ≤ 10 seconds
Output signal: current output type: 4 ~ 20mA (two-wire system) electrical load<400 Ω
Voltage output type: 0 ~ 10V (three wire system) electrical load>10K Ω
Resistance output type: PT100/PT1000 optional
Power supply: 24VDC ± 10%
Cable lock: M16 × 1.5, cable diameter: 4-8mm
Enclosure protection grade: IP54
Temperature sensor probe protection: stainless steel pipe
Working temperature of probe: 0~100 ℃
Working temperature of transmitter: - 20~50 ℃
Storage environment: - 10~+60 ℃, 0~90% RH, no condensation
Applicable medium: water or non corrosive liquid
High anti-interference
Stable performance
Two point calibration
Typical Applications
Automatic building control
Refrigeration system temperature measurement
Temperature measurement of heat exchange system
Industrial and HVAC control
Wiring diagram
Structural drawing
Model Selection Table
Basic unit YGM105-
1 Standardized standard products1
Special customization x
2 Output 4 ~ 20mA 01
0-10V 02
PT100 03
PT1000 04
3. Pipe length L1=210mm, L2=160mm A
L1=250mm,L2=200mm B
Other special customization X
4 Stainless steel outer sleeve pressure interface 1/2NPT 1
Other 2
5 Temperature range 0 ~+50 ℃ 005
0~+100 ℃ 010
Other special customization XXX
Note: When special customization is selected, some technical parameters will also be inconsistent with the technical parameters in this book. Please make a special note when ordering.
Ordering Instructions
YGM105-101A1005
Standardized standard products
Output 4~20mA
Pipe length L1=210mm, L2=160mm
Stainless steel outer sleeve pressure interface 1/2NPT
Temperature range 0~+50 ℃
Statement: The company will continue to innovate the products, and reserves the right to change the design or specifications without prior notice.